?For iron removal from ground water, contact oxidation made under the existence of catalysts and oxidizers is effective. It must be the most effective to use chemicals like chlorine as an oxidizer, but there is a case that chlorine cannot be used. Toyolex F series are contact oxidation filter media developed for air oxidation. They are ideal contact oxidation filter media lowering the running cost by using air as an oxidizer for treatment of industrial and house water that much volume of water is required.
Product | Toyolex F1 | Toyolex F2 |
---|---|---|
Size | 1.4 to 2.3mm | 0.6 to 1.4mm |
Content in size | 75% minimum | |
Appearance | Granular | |
Apparent specific gravity | 0.65 to 0.75g/cm3 | |
Matrix | Ceramics G1 | Ceramics G2 |
Packing: 30L in a PE or craft bag, 0.8m3 in a flexible container bag (Palletizing available)
Note:
* It is required to mix and dissolve raw water and air appropriately before the filter and set the reaction time for the use.
* It takes some time to activate the surface films of filter media for trial operation.
* Be sure to check the dissolved silica content in raw water before design. Much dissolved silica content may cause colloidal iron forming to obstruct iron removal.
* If there was a large quantity of free carbonic acid in raw water, be sure to let carbonic acid gas out of raw water before use.